System

System5

Description The System function block contains information about the function block engine. Also included are statically-bound parameters such as those associated with Modbus.
Availability
  • Requires library: System & I/O
  • Firmware versions 0x1000 and later
savvy-SFD Graphic system5
Graphic with Parameters system5

Parameters

Power Supply Internal Parameter, Read-only, Analog (signed 16-bit integer)
0.0 V to 32.8 V
Timebase Setpoint Internal Parameter, Read-only, Analog (unsigned 16-bit integer)
1 ms to 10000 ms
Desired cycle time.
Timebase Measured Internal Parameter, Read-only, Analog (unsigned 16-bit integer)
0.0 ms to 13107.0 ms
Unfiltered cycle time. This includes the FBE execution time and the overhead (e.g. I/O Modbus, etc.)
Execute Time Internal Parameter, Read-only, Analog (unsigned 16-bit integer)
0.0 ms to 13107.0 ms
0 = < 200 µs
Unfiltered execute time. This is the FBE execution time ignoring overhead.
Program Line Number Internal Parameter, Read-only, Analog (signed 16-bit integer)
0 to 512
Length of program or line at which load error occurred
Program Status Internal Parameter, Read-only, Enumerated (signed 16-bit integer)
-2 = Timebase Overrun
-1 = Phantom
0 = Unterminated Program
1 = OK
2 = Unknown Type
3 = Unknown Function Block
4 = Parameter Out of Range
5 = Already has an Incoming
6 = Outgoing Out Of Range
7 = Incoming Out Of Range
8 = Incoming Already Used
9 = Outgoing Phase Error
10 = Outgoing Already Used
11 = Parameter Not Bound
12 = Outgoing Not Allowed
13 = Incoming Not Allowed
14 = Function Block Collision
15 = Function Block Outside Capability
16 = Function Block Not Owned
17 = System Block Error
18 = Resource Conflict
19 = Associated FB is Wrong Type
20 = Associated FB Must be Defined
21 = Parameter Data Out Of Range
22 = Timebase Too Long
23 = Associated FB is Misaligned
24 = Out of Pool Memory
25 = Unknown Initialization Mode
26 = Invalid Capabilities
27 = Singleton Conflict
28 = Incompatible Function Block
29 = Resource Not Present
30 = Too Many Modbus Registers
Logging Detail Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
0 = Normal
4096 = Verbose
8192 = Meticulous
Temperature Internal Parameter, Read-only, Analog (signed 16-bit integer)
-40 °C to 85 °C
Modbus Slave Indirect 0 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 1 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 2 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 3 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 4 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 5 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 6 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
Modbus Slave Indirect 7 Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
0 to 65535
ModbusTCP Slave Port Internal Parameter, Read-write, Analog (unsigned 16-bit integer)
1 to 49151
502 = Standard (502)
ModbusRTU Slave Speed Internal Parameter, Read-write, Enumerated (signed 16-bit integer)
50 = 50 b/s
75 = 75 b/s
110 = 110 b/s
150 = 150 b/s
300 = 300 b/s
600 = 600 b/s
1200 = 1200 b/s
2400 = 2400 b/s
4800 = 4800 b/s
7200 = 7200 b/s
9600 = 9600 b/s
14400 = 14.4 kb/s
19200 = 19.2 kb/s
ModbusRTU Slave Address Internal Parameter, Read-write, Analog (signed 16-bit integer)
1 to 247